EHBX04CB3V / ERLQ004CAV3 EHBX08CB3V / ERLQ006CAV3 EHBX08CB9W / ERLQ006CAV3 EHBX08CB3V / ERLQ008CAV3 EHBX08CB9W / ERLQ008CAV3 EHBX11CB3V / ERLQ011CAV3 EHBX11CB9W / ERLQ011CAV3 EHBX16CB3V / ERLQ014CAV3 EHBX16CB9W / ERLQ014CAV3 EHBX16CB9W / ERLQ016CAV3 EHBX16CB3V / ERLQ016CAV3
Puissance calorifique Min. kW 1.80 (1) 1.80 (1) 1.80 (1) 1.80 (1) 1.80 (1)            
  Nom. kW 4.40 (1), 4.03 (2) 6.00 (1), 5.67 (2) 6.00 (1), 5.67 (2) 7.40 (1), 6.89 (2) 7.40 (1), 6.89 (2) 11.2 (1), 11.0 (2) 11.2 (1), 11.0 (2) 14.5 (1), 13.6 (2) 14.5 (1), 13.6 (2) 16.0 (1), 15.2 (2) 16.0 (1), 15.2 (2)
  Max. kW 5.12 (1), 4.90 (2) 8.35 (1), 7.95 (2) 8.35 (1), 7.95 (2) 10.0 (1), 9.53 (2) 10.0 (1), 9.53 (2) 8.60 (3), 8.60 (4) 8.60 (3), 8.60 (4) 10.6 (3), 10.8 (4) 10.6 (3), 10.8 (4) 11.4 (3), 10.9 (4) 11.4 (3), 10.9 (4)
Puissance frigorifique Min. kW 2.00 (1), 2.00 (2) 2.50 (1), 2.50 (2) 2.50 (1), 2.50 (2) 2.50 (1), 2.50 (2) 2.50 (1), 2.50 (2)            
  Nom. kW 4.08 (1), 4.17 (2) 5.88 (1), 4.84 (2) 5.88 (1), 4.84 (2) 6.20 (1), 5.36 (2) 6.20 (1), 5.36 (2) 12.1 (1), 11.7 (2) 12.1 (1), 11.7 (2) 12.7 (1), 12.6 (2) 12.7 (1), 12.6 (2) 13.8 (1), 13.1 (2) 13.8 (1), 13.1 (2)
Puissance absorbée Chauffage Nom. kW 0.870 (1), 1.13 (2) 1.27 (1), 1.59 (2) 1.27 (1), 1.59 (2) 1.66 (1), 2.01 (2) 1.66 (1), 2.01 (2) 2.43 (1), 3.10 (2) 2.43 (1), 3.10 (2) 3.37 (1), 4.10 (2) 3.37 (1), 4.10 (2) 3.76 (1), 4.66 (2) 3.76 (1), 4.66 (2)
    Max. kW           3.13 (3), 4.10 (4) 3.13 (3), 4.10 (4) 4.00 (3), 5.19 (4) 4.00 (3), 5.19 (4) 4.32 (3), 5.22 (4) 4.32 (3), 5.22 (4)
  Rafraîchissement Nom. kW 0.900 (1), 1.80 (2) 1.51 (1), 2.07 (2) 1.51 (1), 2.07 (2) 1.64 (1), 2.34 (2) 1.64 (1), 2.34 (2) 3.05 (1), 4.31 (2) 3.05 (1), 4.31 (2) 3.21 (1), 5.08 (2) 3.21 (1), 5.08 (2) 3.74 (1), 5.73 (2) 3.74 (1), 5.73 (2)
COP 5.04 (1), 3.58 (2) 4.74 (1), 3.56 (2) 4.74 (1), 3.56 (2) 4.45 (1), 3.42 (2) 4.45 (1), 3.42 (2)            
EER 4.55 (1), 2.32 (2) 3.89 (1), 2.34 (2) 3.89 (1), 2.34 (2) 3.79 (1), 2.29 (2) 3.79 (1), 2.29 (2)            
Pompe Unité à PSE nominale Rafraîchissement kPa 55.0 (3), 47.0 (4) 55.0 (3), 39.0 (4) 55.0 (3), 39.0 (4) 50.0 (3), 38.0 (4) 50.0 (3), 38.0 (4) 33.0 (5), 3.00 (6) 33.0 (5), 3.00 (6) 64.0 (5), 32.0 (6) 64.0 (5), 32.0 (6) 61.0 (5), 23.0 (6) 61.0 (5), 23.0 (6)
    Chauffage kPa 53.0 (5), 56.0 (6) 45.0 (5), 48.0 (6) 45.0 (5), 48.0 (6) 33.0 (5), 38.0 (6) 33.0 (5), 38.0 (6) 37.0 (7), 39.0 (8) 37.0 (7), 39.0 (8) 49.0 (7), 57.0 (8) 49.0 (7), 57.0 (8) 33.0 (7), 42.0 (8) 33.0 (7), 42.0 (8)
Échangeur de chaleur - côté eau Débit d'eau Rafraîchissement Nom. L/min 12.0 (3), 14.3 (4) 13.9 (3), 19.4 (4) 13.9 (3), 19.4 (4) 15.4 (3), 19.7 (4) 15.4 (3), 19.7 (4) 33.6 (5), 43.1 (6) 33.6 (5), 43.1 (6) 36.0 (5), 46.0 (6) 36.0 (5), 46.0 (6) 37.6 (5), 48.0 (6) 37.6 (5), 48.0 (6)
    Chauffage Nom. L/min 12.6 (5), 11.6 (6) 17.2 (5), 16.3 (6) 17.2 (5), 16.3 (6) 21.2 (5), 19.8 (6) 21.2 (5), 19.8 (6) 32.1 (7), 31.5 (8) 32.1 (7), 31.5 (8) 41.6 (7), 39.0 (8) 41.6 (7), 39.0 (8) 45.9 (7), 43.6 (8) 45.9 (7), 43.6 (8)
Général Coordonnées du fournisseur/fabricant Nom et adresse   Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium            
    Nom ou marque de commerce   Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V.            
  Description du produit Pompe à chaleur air-eau   Oui Oui Oui Oui Oui            
    Pompe à chaleur saumure-eau   non non non non non            
    Système combiné de chauffage pompe à chaleur   non non non non non            
    Pompe à chaleur basse température   non non non non non            
    Réchauffeur supplémentaire intégré   Oui Oui Oui Oui Oui            
    Pompe à chaleur eau-eau   non non non non non            
  Niveau de puissance acoustique LW(A) (conformément à la norme EN14825) Intérieur dB(A) 40.0 40.0 40.0 40.0 40.0 41.0 41.0 44.0 44.0 44.0 44.0
LW(A) - Niveau de puissance sonore (selon EN14825) Unité extérieure dB(A) 61.0 62.0 62.0 62.0 62.0 64.0 64.0 64.0 64.0 66.0 66.0
Condition sonore Étiquette d'écoconception et énergétique Puissance sonore en mode chauffage mesurée conformément à la norme EN12102 dans les conditions de la norme EN14825 Puissance sonore en mode chauffage mesurée conformément à la norme EN12102 dans les conditions de la norme EN14825 Puissance sonore en mode chauffage mesurée conformément à la norme EN12102 dans les conditions de la norme EN14825 Puissance sonore en mode chauffage mesurée conformément à la norme EN12102 dans les conditions de la norme EN14825 Puissance sonore en mode chauffage mesurée conformément à la norme EN12102 dans les conditions de la norme EN14825            
Chauffage d'ambiance - général Unité air-eau Débit d'air nominal (unité extérieure) m³/h 2,700 2,820 2,820 2,820 2,820 5,400 5,400 5,400 5,400 5,400 5,400
  Unité saumure/eau-eau Débit nominal eau/saumure m³/h   0.00   0.00 0.00            
  Autre Commande de puissance   Inverter Inverter Inverter Inverter Inverter            
    Cdh (dégradation chauffage)   1.00 1.00 1.00 1.00 1.00            
    Pck (mode résistance de carter) kW 0.00 0.00 0.00 0.00 0.00 0.055 0.055 0.055 0.055 0.055 0.055
    Poff (mode arrêt) kW 0.0080 0.0080 0.0080 0.0080 0.0080 0.055 0.055 0.055 0.055 0.055 0.055
    Psb (mode veille) kW 0.0080 0.0080 0.0080 0.0080 0.0080 0.055 0.055 0.055 0.055 0.055 0.055
    Pto (thermostat désactivé) kW 0.0060 0.0070 0.0070 0.0080 0.0080 0.057 0.057 0.057 0.057 0.057 0.057
  Dispositif de chauffage supplémentaire intégré Émission de NOx mg/kWh 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
    Psup kW 3.00 3.00 9.00 3.00 9.00 3.00 9.00 3.00 9.00 9.00 3.00
    Type d'intrant énergétique   Électrique Électrique Électrique Électrique Électrique            
Chauffage d'eau chaude sanitaire Général Fonction pour régler le chauffage de l'eau en dehors des heures de pic   Oui Oui Oui Oui Oui            
Chauffage d'ambiance Sortie d'eau sous climat tempéré : 55 °C Général SCOP   3.20 3.22 3.22 3.20 3.20            
      Cons. énergétique annuelle kWh 2,360 3,370 3,370 4,100 4,100 6,260 6,260 7,900 7,900 8,970 8,970
      Efficacité saisonnière du chauffage d'ambiance % 125 126 126 125 125 120 120 123 123 119 119
      Pnom à -10 °C kW 3.70 5.30 5.30 6.40 6.40 9.99 9.99 12.7 12.7 13.9 13.9
      Consommation énergétique annuelle Qhe (PCS) Gj (2) 8.48 12.1 12.1 14.8 14.8 22.6 22.6 28.4 28.4 32.3 32.3
      Classe d'effic. saisonnière du chauffage d'ambiance   A++ A++ A++ A++ A++            
    Condition A (-7 °CBS/-8 °CBH) Cdh (dégradation chauffage)   1.00 1.00 1.00 1.00 1.00            
      COPd   2.03 2.02 2.02 1.98 1.98            
      Pdh kW 3.36 4.56 4.56 5.50 5.50 8.83 8.83 9.97 9.97 12.2 12.2
      PERd % 81.2 80.8 80.8 79.2 79.2 79.6 79.6 70.4 70.4 71.2 71.2
    Condition B (2 °CBS/1 °CBH) Cdh (dégradation chauffage)   1.00 0.990 0.990 1.00 1.00            
      COPd   3.08 3.17 3.17 3.17 3.17            
      Pdh kW 2.00 3.43 3.43 3.43 3.43 5.28 5.28 6.76 6.76 7.61 7.61
      PERd % 123 127 127 127 127 130 130 142 142 125 125
    Condition C (7 °CBS/6 °CBH) Cdh (dégradation chauffage)   0.990 0.990 0.990 0.990 0.990            
      COPd   4.27 4.20 4.20 4.20 4.20            
      Pdh kW 2.77 3.51 3.51 3.50 3.50 4.47 4.47 4.66 4.66 4.83 4.83
      PERd % 171 168 168 168 168 172 172 169 169 176 176
    Condition D (12 °CBS/11 °CBH) Cdh (dégradation chauffage)   0.990 0.990 0.990 0.990 0.990            
      COPd   6.33 5.82 5.82 5.82 5.82            
      Pdh kW 2.65 3.28 3.28 3.28 3.28 5.37 5.37 5.26 5.26 5.38 5.38
      PERd % 253 233 233 233 233 256 256 218 218 254 254
    Tol (limite de température de fonctionnement) COPd   1.80 1.74 1.74 1.74 1.74            
      Pdh kW 3.76 3.10 3.10 3.10 3.10 9.08 9.08 12.2 12.2 13.3 13.3
      PERd % 72.0 69.6 69.6 69.6 69.6 71.6 71.6 70.0 70.0 68.4 68.4
      TOL °C -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0
      WTOL °C 55.0 55.0 55.0 55.0 55.0 55.0 55.0 55.0 55.0 55.0 55.0
    Cap. suppl. puiss. calorif. nom. Psup (à Tconception -10 °C) kW 0.00 2.20 2.20 3.30 3.30 0.910 0.910 0.550 0.550 0.580 0.580
    Tbiv (température bivalente) COPd   1.80 1.87 1.87 1.98 1.98            
      Pdh kW 3.76 4.90 4.90 5.50 5.50 8.83 8.83 11.0 11.0 12.2 12.2
      PERd % 72.0 74.8 74.8 79.2 79.2 79.6 79.6 76.8 76.8 71.2 71.2
      Tbiv °C -10.0 -8.00 -8.00 -7.00 -7.00 -7.00 -7.00 -6.00 -6.00 -7.00 -7.00
  Sortie d'eau climat froid : 55 °C Général Consommation énergétique annuelle kWh 2,130 2,310 2,310 3,090 3,090 6,740 6,740 7,870 7,870 8,580 8,580
      Efficacité saisonnière du chauffage d'ambiance % 107 107 107 110 110 95.0 95.0 95.5 95.5 98.3 98.3
      Pnom à -22°C kW 2.39 2.60 2.60 3.56 3.56 6.99 6.99 8.15 8.15 9.12 9.12
      Consommation énergétique annuelle Qhe (PCS) Gj (2) 7.68 8.30 8.30 11.1 11.1 24.3 24.3 28.3 28.3 30.9 30.9
  Climat chaud - sortie d'eau à 55 °C Général Cons. énergétique annuelle kWh 1,170 1,490 1,490 1,840 1,840 2,630 2,630 3,270 3,270 3,420 3,420
      Ƞs (effic. saisonnière du chauffage d'ambiance) % 186 182 182 178 178 125 125 135 135 136 136
      Pnom à 2°C kW 4.27 5.30 5.30 6.36 6.36 7.58 7.58 9.84 9.84 10.3 10.3
      Consommation énergétique annuelle Qhe (PCS) Gj (2) 4.20 5.37 5.37 6.62 6.62 9.47 9.47 11.8 11.8 12.3 12.3
  Sortie d'eau climat tempéré 35 °C Général SCOP   4.52 4.29 4.29 4.34 4.34            
      Cons. énergétique annuelle kWh 1,980 2,540 2,540 3,490 3,490 5,380 5,380 7,250 7,250 8,270 8,270
      Ƞs (effic. saisonnière du chauffage d'ambiance) % 178 169 169 171 171 156 156 153 153 149 149
      Pnominal à -10 °C kW 4.40 5.34 5.34 7.40 7.40 11.2 11.2 14.5 14.5 16.0 16.0
      Consommation énerg. annuelle Qhe (GCV) Gj (2) 7.13 9.14 9.14 12.6 12.6 19.4 19.4 26.1 26.1 29.8 29.8
      Classe d'eff. saisonnière du chauffage d'ambiance   A++ A++ A++ A++ A++            
    Condition A(-7°CBS/-8°CBH) COPd   3.01 2.69 2.69 2.69 2.69            
      Pdh kW 4.01 4.72 4.72 6.68 6.68 8.88 8.88 10.7 10.7 12.4 12.4
      PERd % 120 108 108 108 108 105 105 105 105 93.2 93.2
    Condition B (2° CBS/1° CBH) Cdh (dégradation chauffage)   1.00 0.990 0.990 1.00 1.00            
      COPd   4.41 4.24 4.24 4.24 4.24            
      Pdh kW 2.40 3.90 3.90 3.90 3.90 6.03 6.03 7.71 7.71 8.62 8.62
      PERd % 176 170 170 170 170 162 162 163 163 150 150
    Condition C (7 °CBS/6 °CBH) Cdh (dégradation chauffage)   0.980 0.980 0.980 1.00 1.00            
      COPd   5.85 5.75 5.75 5.75 5.75            
      Pdh kW 1.70 2.59 2.59 2.59 2.59 5.74 5.74 5.05 5.05 5.74 5.74
      PERd % 234 230 230 230 230 271 271 228 228 271 271
    Condition D (12 °CBS/11 °CBH) Cdh (dégradation chauffage)   0.980 0.980 0.980 0.980 0.980            
      COPd   7.71 7.27 7.27 7.27 7.27            
      Pdh kW 2.04 2.61 2.61 2.61 2.61 6.50 6.50 5.16 5.16 6.50 6.50
      PERd % 308 291 291 291 291 359 359 268 268 359 359
    Tol (limite de température de fonctionnement) COPd   2.61 2.29 2.29 2.29 2.29            
      Pdh kW 4.36 4.70 4.70 6.81 6.81 8.76 8.76 12.6 12.6 11.7 11.7
      PERd % 104 91.6 91.6 91.6 91.6 93.6 93.6 104 104 82.0 82.0
      TOL °C -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0
      WTOL °C 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0
    Condition G (-15 °CBS/-) COPd   0.00 0.00 0.00 0.00 0.00            
      Pdh kW 0.00 0.00 0.00 0.00 0.00            
      PERd % 0.00 0.00 0.00 0.00 0.00            
    Tbiv (température bivalente) COPd   2.61 2.47 2.47 2.47 2.47            
      Pdh kW 4.36 4.93 4.93 7.14 7.14 9.09 9.09 11.6 11.6 12.1 12.1
      PERd % 104 98.8 98.8 98.8 98.8 113 113 113 113 102 102
      Tbiv °C -10.0 -8.00 -8.00 -8.00 -8.00 -5.00 -5.00 -5.00 -5.00 -4.00 -4.00
    Sortie calorifique nom. - Puiss. suppl. Psup (à Tconception -10 °C) kW 0.040 0.640 0.640 0.590 0.590 2.44 2.44 1.93 1.93 4.35 4.35
  Sortie d'eau climat froid 35 °C Général Consommation énergétique annuelle kWh 1,480 2,040 2,040 2,480 2,480 6,430 6,430 8,170 8,170 9,050 9,050
      Ƞs (efficacité saisonnière du chauffage d'ambiance) % 147 153 153 151 151 148 148 141 141 137 137
      Pnom à -22°C kW 2.28 3.25 3.25 3.89 3.89 10.3 10.3 12.3 12.3 13.3 13.3
      Consommation énergétique annuelle Qhe (PCS) Gj (2) 5.32 7.34 7.34 8.91 8.91 23.1 23.1 29.4 29.4 32.6 32.6
  Sortie d'eau en conditions climatiques chaudes 35 °C Général Cons. énergétique annuelle kWh 905 1,270 1,270 1,570 1,570 1,950 1,950 2,350 2,350 2,480 2,480
      Ƞs (effic. saisonnière du chauffage d'ambiance) % 269 259 259 251 251 192 192 199 199 199 199
      Pnom à 2°C kW 4.81 6.40 6.40 7.68 7.68 9.06 9.06 10.9 10.9 11.4 11.4
      Consommation énerg. annuelle Qhe (GCV) Gj (2) 3.26 4.56 4.56 5.67 5.67 7.02 7.02 8.46 8.46 8.92 8.92
Remarques Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C) Condition 1 : rafraîchissement Ta 35 °C - LWE 18 °C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 35 °C (DT = 5 °C)
  Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C) Condition 2 : rafraîchissement Ta 35 °C - LWE 7°C (DT = 5 °C) ; chauffage Ta BS/BH 7 °C/6 °C - LWC 45 °C (DT = 5 °C)
  Tamb 35 °C - LWE 7 °C (DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C) Condition 3 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 35 °C Condition 3 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 35 °C Condition 3 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 35 °C Condition 3 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 35 °C Condition 3 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 35 °C Condition 3 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 35 °C
  Tamb 35 °C - LWE 18°C (DT=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C) Condition 4 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 45 °C Condition 4 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 45 °C Condition 4 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 45 °C Condition 4 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 45 °C Condition 4 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 45 °C Condition 4 : chauffage Ta BS -7 °C (HR : 85 %) - LWC 45 °C
  BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C) Tamb 35 °C - LWE 7 °C (DT=5 °C)
  BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C) Tamb 35 °C - LWE 18°C (DT=5 °C)
Chauffage d'ambiance - général Autre Commande de puissance           1.00 1.00 1.00 1.00 1.00 1.00
  Dispositif de chauffage supplémentaire intégré Type d'intrant énergétique           Électrique Électrique Électrique Électrique Électrique Électrique
Chauffage d'ambiance Sortie d'eau climat tempéré 35 °C Condition A(-7°CBS/-8°CBH) COPd           2.63 2.63 2.63 2.63 2.33 2.33
    Condition C (7 °CBS/6 °CBH) COPd           0.940 0.940 1.00 1.00 0.940 0.940
    Condition D (12 °CBS/11 °CBH) COPd           0.920 0.920 0.930 0.930 0.920 0.920
    Général Classe d'eff. saisonnière du chauffage d'ambiance           3.98 3.98 3.90 3.90 3.80 3.80
    Condition B (2° CBS/1° CBH) COPd           1.00 1.00 1.00 1.00 1.00 1.00
    Tbiv (température bivalente) COPd           2.82 2.82 2.83 2.83 2.56 2.56
    Tol (limite de température de fonctionnement) COPd           2.34 2.34 2.60 2.60 2.05 2.05
  Sortie d'eau sous climat tempéré : 55 °C Condition A (-7 °CBS/-8 °CBH) COPd           1.00 1.00 1.00 1.00 1.00 1.00
    Tbiv (température bivalente) COPd           1.99 1.99 1.92 1.92 1.78 1.78
    Tol (limite de température de fonctionnement) COPd           1.79 1.79 1.75 1.75 1.71 1.71
    Général Classe d'effic. saisonnière du chauffage d'ambiance           3.09 3.09 3.16 3.16 3.06 3.06
    Condition B (2 °CBS/1 °CBH) COPd           1.00 1.00 1.00 1.00 1.00 1.00
    Condition C (7 °CBS/6 °CBH) COPd           0.950 0.950 0.950 0.950 1.00 1.00
    Condition D (12 °CBS/11 °CBH) COPd           0.930 0.930 0.940 0.940 0.930 0.930
Général Coordonnées du fournisseur/fabricant Nom et adresse           Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V.
  Description du produit Pompe à chaleur basse température           non non non non non non
Condition sonore Étiquette d'écoconception et énergétique           3.98 (1), 2.72 (2) 3.98 (1), 2.72 (2) 3.96 (1), 2.47 (2) 3.96 (1), 2.47 (2) 3.69 (1), 2.29 (2) 3.69 (1), 2.29 (2)
Remarques           BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C) BS/BH 7 °C/6 °C-LWC 35 °C(DT=5 °C)
            BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C) BS/BH 7 °C/6 °C - LWC 45 °C(Dt=5 °C)