EAVX16S23DA6V / EPGA11DAV3 EAVX16S18DA6V / EPGA11DAV3 EAVX16S23DA6V / EPGA14DAV3 EAVX16S18DA6V / EPGA14DAV3 EAVX16S23DA6V / EPGA16DAV3 EAVX16S18DA6V / EPGA16DAV3
Binnenunit EAVX16S23DA6V EAVX16S18DA6V EAVX16S23DA6V EAVX16S18DA6V EAVX16S23DA6V EAVX16S18DA6V
Buitenunit EPGA11DAV3 EPGA11DAV3 EPGA14DAV3 EPGA14DAV3 EPGA16DAV3 EPGA16DAV3
Verwarmingscapaciteit Nom. kW 11.1 (1), 11.3 (2) 11.1 (1), 11.3 (2) 14.5 (1), 14.5 (2) 14.5 (1), 14.5 (2) 16.5 (1), 15.6 (2) 16.5 (1), 15.6 (2)
Koelcapaciteit Nom. kW 10.5 (1), 10.7 (2) 10.5 (1), 10.7 (2) 11.1 (1), 11.9 (2) 11.1 (1), 11.9 (2) 13.5 (1), 11.9 (2) 13.5 (1), 11.9 (2)
Opgenomen vermogen Verwarmen Nom. kW 2.16 (1), 2.91 (2) 2.16 (1), 2.91 (2) 2.91 (1), 3.96 2.91 (1), 3.96 3.45 (1), 4.21 (2) 3.45 (1), 4.21 (2)
  Koelen Nom. kW 2.21 (1), 3.30 (2) 2.21 (1), 3.30 (2) 2.72 (1), 3.97 (2) 2.72 (1), 3.97 (2) 3.42 (1), 3.97 (2) 3.42 (1), 3.97 (2)
  Sanitair warm water van 10°C tot 50°C Nom. kWu 3.08 2.67 3.08 2.67 3.08 2.67
Heat up time from 10°C to 50°C hr 1h02min at 7°C ambient temperature 53min at 7°C ambient temperature 1h02min at 7°C ambient temperature 53min at 7°C ambient temperature 1h02min at 7°C ambient temperature 53min at 7°C ambient temperature
COP 5.15 (1), 3.88 (2) 5.15 (1), 3.88 (2) 4.99 (1), 3.65 (2) 4.99 (1), 3.65 (2) 4.78 (1), 3.71 (2) 4.78 (1), 3.71 (2)
EER 4.75 (1), 3.23 (2) 4.75 (1), 3.23 (2) 4.09 (1), 2.99 (2) 4.09 (1), 2.99 (2) 3.94 (1), 2.99 (2) 3.94 (1), 2.99 (2)
Pomp Type   Grundfos UPMXL GEO 25-125 130 PWM Grundfos UPMXL GEO 25-125 130 PWM Grundfos UPMXL GEO 25-125 130 PWM Grundfos UPMXL GEO 25-125 130 PWM Grundfos UPMXL GEO 25-125 130 PWM Grundfos UPMXL GEO 25-125 130 PWM
  Nominale externe statische druk unit Koelen kPa 81.7 (1), 81.5 (2) 81.7 (1), 81.5 (2) 75.8 (1), 69.7 (2) 75.8 (1), 69.7 (2) 61.5 (1), 69.7 (2) 61.5 (1), 69.7 (2)
    Verwarmen kPa 78.6 (1), 78.9 (2) 78.6 (1), 78.9 (2) 53.8 (1), 52.7 (2) 53.8 (1), 52.7 (2) 40.6 (1), 42.0 (2) 40.6 (1), 42.0 (2)
Warmtewisselaar waterzijde Waterdebiet Koelen Nom. l/min 31.3 (1), 31.3 (2) 31.3 (1), 31.3 (2) 33.6 (1), 35.9 (2) 33.6 (1), 35.9 (2) 38.7 (1), 35.9 (2) 38.7 (1), 35.9 (2)
    Verwarmen Nom. l/min 32.5 (1), 32.4 (2) 32.5 (1), 32.4 (2) 41.2 (1), 41.5 (2) 41.2 (1), 41.5 (2) 45.1 (1), 44.7 (2) 45.1 (1), 44.7 (2)
Algemeen Gegevens van leverancier/fabrikant Naam en adres   Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
    Naam of handelsmerk   Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V. Daikin Europe N.V.
  Productbeschrijving Lucht/water-warmtepomp   Ja Ja Ja Ja Ja Ja
    Glycol/water-warmtepomp   Nee Nee Nee Nee Nee Nee
    Verwarming combinatie warmtepomp   Ja Ja Ja Ja Ja Ja
    Lagetemperatuurswarmtepomp   Nee Nee Nee Nee Nee Nee
    Ingebouwde hulpverwarming   Ja Ja Ja Ja Ja Ja
    Water/water-warmtepomp   Nee Nee Nee Nee Nee Nee
  LW(A) geluidsvermogensniveau (volgens EN14825) Binnen dB(A) 44.0 44.0 44.0 44.0 44.0 44.0
LW(A) geluidsvermogensniveau (volgens EN14825) Buiten dB(A) 64.0 64.0 64.0 64.0 66.0 66.0
Ecodesign geluidsconditie en energielabel Geluidsvermogen in verwarmingsmodus, gemeten volgens EN12102 onder voorwaarden van EN14825 Geluidsvermogen in verwarmingsmodus, gemeten volgens EN12102 onder voorwaarden van EN14825 Geluidsvermogen in verwarmingsmodus, gemeten volgens EN12102 onder voorwaarden van EN14825 Geluidsvermogen in verwarmingsmodus, gemeten volgens EN12102 onder voorwaarden van EN14825 Geluidsvermogen in verwarmingsmodus, gemeten volgens EN12102 onder voorwaarden van EN14825 Geluidsvermogen in verwarmingsmodus, gemeten volgens EN12102 onder voorwaarden van EN14825
Algemene verwarming Lucht/water-unit Nominaal luchtdebiet (buiten) m³/u 6,900 6,900 6,900 6,900 8,100 8,100
  Andere Capaciteitsregeling   Inverter Inverter Inverter Inverter Inverter Inverter
    Pck (carterverwarming aan) kW 0.000 0.000 0.000 0.000 0.000 0.000
    Poff (uitgeschakelde stand) kW 0.021 0.021 0.021 0.021 0.021 0.021
    Psb (in stand-by) kW 0.021 0.021 0.021 0.021 0.021 0.021
    Pto (thermostaat uit) kW 0.041 0.041 0.041 0.041 0.041 0.041
  Ingebouwde hulpverwarming Psup kW 6.0 6.0 6.0 6.0 6.0 6.0
    Type stroomvoorziening   Elektrisch Elektrisch Elektrisch Elektrisch Elektrisch Elektrisch
Verwarming van sanitair warm water Algemeen Aangegevens belastingprofiel   XL L XL L XL L
    Functie voor verwarmen van water tijdens daluren   Ja Ja Ja Ja Ja Ja
  Gematigd klimaat AEC (jaarlijks stroomverbruik) kWu 1,513 1,029 1,513 1,029 1,513 1,029
    AFC (jaarlijks brandstofverbruik) Gj 5.45 3.70 5.45 3.70 5.45 3.70
    Ƞwh (waterverwarmingsrendement) % 112 104 112 104 112 104
    Qelec (dagelijks stroomverbruik) kWu 7.090 4.870 7.090 4.870 7.090 4.870
    Energierendementsklasse waterverwarming   A A A A A A
  Koud klimaat AEC (jaarlijks stroomverbruik) kWu 1,851 1,066 1,851 1,066 1,851 1,066
    AFC (jaarlijks brandstofverbruik) Gj 6.66 3.84 6.66 3.84 6.66 3.84
    Ƞwh (waterverwarmingsrendement) % 91 100 91 100 91 100
    Qelec (dagelijks stroomverbruik) kWu 8.850 5.195 8.850 5.195 8.850 5.195
  Warm klimaat AEC (jaarlijks stroomverbruik) kWu 1,301 749 1,301 749 1,301 749
    AFC (jaarlijks brandstofverbruik) Gj 4.68 2.70 4.68 2.70 4.68 2.70
    Ƞwh (waterverwarmingsrendement) % 130 142 130 142 130 142
    Qelec (dagelijks stroomverbruik) kWu 6.160 3.590 6.160 3.590 6.160 3.590
Centrale verwarming Wateruitlaat gematigd klimaat 55°C Algemeen Jaarlijks energieverbruik kWu 7,768 7,768 8,592 8,592 9,628 9,628
      Seizoensrendement van verwarming % 130 130 132 132 134 134
      Pnominaal bij -10°C kW 13 13 14 14 16 16
      Qhe jaarl. energieverbruik (GCV) Gj 28.0 28.0 30.9 30.9 34.7 34.7
      SCOP   3.32 3.32 3.37 3.37 3.43 3.43
      Seizoensefficiëntieklasse verwarming   A++ A++ A++ A++ A++ A++
    A-conditie (-7°C DB/-8°C NB) Cdh (degradatie-verwarming)   1.0 1.0 1.0 1.0 1.0 1.0
      COPd   2.25 2.25 2.17 2.17 2.23 2.23
      Pdh kW 11.5 11.5 12.3 12.3 13.1 13.1
      PERd % 90.0 90.0 86.8 86.8 89.2 89.2
    B-conditie (-2°C DB/1°C NB) Cdh (degradatie-verwarming)   1.0 1.0 1.0 1.0 1.0 1.0
      COPd   3.14 3.14 3.18 3.18 3.26 3.26
      Pdh kW 6.5 6.5 8.1 8.1 8.7 8.7
      PERd % 125.6 125.6 127.2 127.2 130.4 130.4
    C-conditie (7°C DB/6°C NB) Cdh (degradatie-verwarming)   0.96 0.96 1.0 1.0 1.0 1.0
      COPd   4.27 4.27 4.46 4.46 4.62 4.62
      Pdh kW 4.6 4.6 5.0 5.0 5.8 5.8
      PERd % 170.8 170.8 178.4 178.4 184.8 184.8
    D-conditie (12°C DB/11°C NB) Cdh (degradatie-verwarming)   0.95 0.95 0.95 0.95 0.95 0.95
      COPd   5.75 5.75 5.94 5.94 6.47 6.47
      Pdh kW 5.2 5.2 5.2 5.2 5.2 5.2
      PERd % 230.0 230.0 237.6 237.6 258.8 258.8
    Tol (min./max. bedrijfstemperatuur) COPd   2.11 2.11 2.10 2.10 2.05 2.05
      Pdh kW 12.5 12.5 13.5 13.5 13.2 13.2
      PERd % 84.4 84.4 84.0 84.0 82.0 82.0
      TOL °C -10 -10 -10 -10 -10 -10
      WTOL °C 55 55 55 55 55 55
    Extra capaciteit nominaal verwarmingsvermogen Psup (bij Tontwerp -10°C) kW 0.0 0.0 0.5 0.5 2.8 2.8
    Tbiv (bivalente temperatuur) COPd   2.11 2.11 2.17 2.17 2.40 2.40
      Pdh kW 12.5 12.5 12.3 12.3 12.9 12.9
      PERd % 84.4 84.4 86.8 86.8 96.0 96.0
      Tbiv °C -10 -10 -7 -7 -5 -5
  Wateruitlaat koud klimaat 55°C Algemeen Jaarlijks energieverbruik kWu 10,038 10,038 11,339 11,339 12,249 12,249
      Seizoensrendement van verwarming % 125 125 123 123 121 121
      Pnominaal bij -22°C kW 13 13 15 15 15 15
      Qhe jaarl. energieverbruik (GCV) Gj 36.1 36.1 40.8 40.8 44.1 44.1
    A-conditie (-7°C DB/-8°C NB) Cdh (reductie van verwarming)   1.0 1.0 1.0 1.0 1.0 1.0
      COPd   2.68 2.68 2.61 2.61 2.58 2.58
      Pdh kW 8.3 8.3 8.8 8.8 9.4 9.4
      PERd % 107.2 107.2 104.4 104.4 103.2 103.2
    B-conditie (-2°C DB/1°C NB) Cdh (reductie van verwarming)   1.0 1.0 1.0 1.0 1.0 1.0
      COPd   3.75 3.75 3.75 3.75 3.66 3.66
      Pdh kW 5.1 5.1 5.5 5.5 5.9 5.9
      PERd % 150.0 150.0 150.0 150.0 146.4 146.4
    C-conditie (7°C DB/6°C NB) Cdh (degradatie-verwarming)   0.96 0.96 0.96 0.96 0.96 0.96
      COPd   4.63 4.63 4.70 4.70 4.75 4.75
      Pdh kW 4.5 4.5 4.5 4.5 4.5 4.5
      PERd % 185.2 185.2 188.0 188.0 190.0 190.0
    D-conditie (12°C DB/11°C NB) COPd   6.01 6.01 6.13 6.13 6.21 6.21
      Pdh kW 5.2 5.2 5.2 5.2 5.1 5.1
      PERd % 240.4 240.4 245.2 245.2 248.4 248.4
    Tol (min./max. bedrijfstemperatuur) COPd   1.34 1.34 1.34 1.34 1.34 1.34
      Pdh kW 7.5 7.5 7.5 7.5 7.5 7.5
      PERd % 53.6 53.6 53.6 53.6 53.6 53.6
      TOL °C -21 -21 -21 -21 -21 -21
      WTOL °C 54 54 54 54 54 54
    G-conditie (-15°C DB/-) COPd   2.10 2.10 2.12 2.12 2.13 2.13
      Pdh kW 11.1 11.1 11.9 11.9 12.6 12.6
      PERd % 84.0 84.0 84.8 84.8 85.2 85.2
    Tbiv (bivalente temperatuur) COPd   1.93 1.93 2.05 2.05 2.13 2.13
      Pdh kW 11.4 11.4 12.4 12.4 12.6 12.6
      PERd % 77.2 77.2 82.0 82.0 85.2 85.2
      Tbiv °C -18 -18 -16 -16 -15 -15
    Extra capaciteit nominaal verwarmingsvermogen Psup (bij Tontwerp -22°C) kW 5.5 5.5 7.0 7.0 7.9 7.9
  Wateruitlaat warm klimaat 55°C Algemeen Jaarlijks energieverbruik kWu 3,603 3,603 4,012 4,012 4,270 4,270
      Ƞs (seizoensefficiëntie ruimteverwarming) % 160 160 164 164 166 166
      Pnominaal bij 2°C kW 11 11 13 13 14 14
      Qhe jaarl. energieverbruik (GCV) Gj 13.0 13.0 14.4 14.4 15.4 15.4
    B-conditie (-2°C DB/1°C NB) Cdh (reductie van verwarming)   1.0 1.0 1.0 1.0 1.0 1.0
      COPd   2.45 2.45 2.43 2.43 2.41 2.41
      Pdh kW 11.4 11.4 12.4 12.4 13.5 13.5
      PERd % 98.0 98.0 97.2 97.2 96.4 96.4
    C-conditie (7°C DB/6°C NB) Cdh (degradatie-verwarming)   1.0 1.0 1.0 1.0 1.0 1.0
      COPd   3.58 3.58 3.62 3.62 3.66 3.66
      Pdh kW 7.2 7.2 7.9 7.9 8.7 8.7
      PERd % 143.2 143.2 144.8 144.8 146.4 146.4
    D-conditie (12°C DB/11°C NB) Cdh (reductie van verwarming)   0.96 0.96 0.96 0.96 0.96 0.96
      COPd   5.16 5.16 5.29 5.29 5.38 5.38
      Pdh kW 5.3 5.3 5.2 5.2 5.2 5.2
      PERd % 206.4 206.4 211.6 211.6 215.2 215.2
    Tbiv (bivalente temperatuur) COPd   2.45 2.45 2.43 2.43 2.41 2.41
      Pdh kW 11.4 11.4 12.4 12.4 13.5 13.5
      PERd % 98.0 98.0 97.2 97.2 96.4 96.4
      Tbiv °C 2 2 2 2 2 2
  Wateruitlaat gematigd klimaat 35°C Algemeen SCOP   4.44 4.44 4.51 4.51 4.61 4.61
      Jaarlijks energieverbruik kWu 5,112 5,112 5,720 5,720 6,267 6,267
      Ƞs (seizoensefficiëntie ruimteverwarming) % 175 175 178 178 182 182
      Pnominaal -10°C kW 11 11 13 13 14 14
      Qhe jaarl. energieverbruik (GCV) Gj 18.4 18.4 20.6 20.6    
      Seizoensrendementsklasse verwarming   A++ A++ A++ A++ A++ A++
    A-conditie (-7°C DB/-8°C NB) COPd   3.07 3.07 2.85 2.85 2.99 2.99
      Pdh kW 9.7 9.7 11.1 11.1 12.2 12.2
      PERd % 122.8 122.8 114.0 114.0 119.6 119.6
    B-conditie (2°C DB/1°C NB) Cdh (degradatie-verwarming)   1.0 1.0 1.0 1.0 1.0 1.0
      COPd   4.15 4.15 4.24 4.24 4.30 4.30
      Pdh kW 6.3 6.3 7.0 7.0 7.4 7.4
      PERd % 166.0 166.0 169.6 169.6 172.0 172.0
    C-conditie (7°C DB/6°C NB) Cdh (degradatie-verwarming)   0.95 0.95 1.0 1.0 0.95 0.95
      COPd   5.86 5.86 6.24 6.24 6.35 6.35
      Pdh kW 4.5 4.5 4.5 4.5 5.0 5.0
      PERd % 234.4 234.4 249.6 249.6 254.0 254.0
    D-conditie (12°C DB/11°C NB) Cdh (reductie van verwarming)   0.94 0.94 0.94 0.94 0.94 0.94
      COPd   7.88 7.88 8.12 8.12 8.12 8.12
      Pdh kW 5.3 5.3 5.3 5.3 5.3 5.3
      PERd % 315.2 315.2 324.8 324.8 324.8 324.8
    TOL (bedrijfstemperatuur) COPd   2.80 2.80 2.53 2.53 2.72 2.72
      Pdh kW 11.0 11.0 12.5 12.5 14.5 14.5
      PERd % 112.0 112.0 101.2 101.2 108.8 108.8
      TOL °C -10 -10 -10 -10 -10 -10
      WTOL °C 35 35 35 35 35 35
    Tbiv (bivalente temperatuur) COPd   2.80 2.80 2.53 2.53 2.72 2.72
      Pdh kW 11.0 11.0 12.5 12.5 14.5 14.5
      PERd % 112.0 112.0 101.2 101.2 108.8 108.8
      Tbiv °C -10 -10 -10 -10 -10 -10
    Nom. bijkomend verwarmingsvermogen Psup (bij Tontwerp -10°C) kW 0.0 0.0 0.0 0.0 0.0 0.0
  Wateruitlaat koud klimaat 35°C Algemeen Jaarlijks energieverbruik kWu 9,249 9,249 10,202 10,202 11,061 11,061
      Ƞs (seizoensefficiëntie ruimteverwarming) % 152 152 152 152 157 157
      Pnominaal bij -22°C kW 15 15 16 16 18 18
      Qhe jaarl. energieverbruik (GCV) Gj 33.3 33.3 36.7 36.7 39.8 39.8
    A-conditie (-7°C DB/-8°C NB) COPd   3.09 3.09 3.20 3.20 3.39 3.39
      Pdh kW 9.0 9.0 9.7 9.7 10.8 10.8
      PERd % 123.6 123.6 128.0 128.0 135.6 135.6
    B-conditie (2°C DB/1°C NB) Cdh (reductie van verwarming)   1.0 1.0 1.0 1.0 0.97 0.97
      COPd   4.45 4.45 4.45 4.45 4.68 4.68
      Pdh kW 5.6 5.6 5.6 5.6 7.1 7.1
      PERd % 178.0 178.0 178.0 178.0 187.2 187.2
    C-conditie (7°C DB/6°C NB) Cdh (degradatie-verwarming)   0.94 0.94 0.94 0.94 0.94 0.94
      COPd   6.24 6.24 6.46 6.46 6.75 6.75
      Pdh kW 4.5 4.5 4.5 4.5 4.6 4.6
      PERd % 249.6 249.6 258.4 258.4 270.0 270.0
    D-conditie (12°C DB/11°C NB) Cdh (reductie van verwarming)   0.94 0.94 0.94 0.94 0.94 0.94
      COPd   7.84 7.84 7.98 7.98 8.19 8.19
      Pdh kW 5.2 5.2 5.3 5.3 5.3 5.3
      PERd % 313.6 313.6 319.2 319.2 327.6 327.6
    Tol (min./max. bedrijfstemperatuur) COPd   2.13 2.13 2.10 2.10 2.10 2.10
      Pdh kW 11.8 11.8 13.5 13.5 13.5 13.5
      PERd % 85.2 85.2 84.0 84.0 84.0 84.0
      TOL °C -22 -22 -22 -22 -22 -22
      WTOL °C 35 35 35 35 35 35
    G-conditie (-15°C DB/-) COPd   2.67 2.67 2.43 2.43 2.40 2.40
      Pdh kW 12.1 12.1 13.4 13.4 14.6 14.6
      PERd % 106.8 106.8 97.2 97.2 96.0 96.0
    Tbiv (bivalente temperatuur) COPd   2.49 2.49 2.36 2.36 2.40 2.40
      Pdh kW 13.1 13.1 13.7 13.7 14.6 14.6
      PERd % 99.6 99.6 94.4 94.4 96.0 96.0
      Tbiv °C -18 -18 -16 -16 -15 -15
    Nominaal bijkomend verwarmingsvermogen Psup (bij Tontwerp -22°C) kW 2.7 2.7 2.5 2.5 4.5 4.5
  Wateruitlaat warm klimaat 35°C Algemeen Jaarlijks energieverbruik kWu 2,403 2,403 2,687 2,687 3,044 3,044
      Ƞs (seizoensefficiëntie ruimteverwarming) % 242 242 246 246 243 243
      Pnominaal bij 2°C kW 11 11 13 13 14 14
      Qhe jaarl. energieverbruik (GCV) Gj 8.65 8.65 9.67 9.67 11.0 11.0
    B-conditie (2°C DB/1°C NB) Cdh (reductie van verwarming)   1.0 1.0 1.0 1.0 1.0 1.0
      COPd   3.40 3.40 3.25 3.25 3.22 3.22
      Pdh kW 11.1 11.1 12.4 12.4 12.7 12.7
      PERd % 136.0 136.0 130.0 130.0 128.8 128.8
    C-conditie (7°C DB/6°C NB) Cdh (degradatie-verwarming)   1.0 1.0 1.0 1.0 1.0 1.0
      COPd   5.67 5.67 5.70 5.70 5.73 5.73
      Pdh kW 7.6 7.6 8.4 8.4 9.3 9.3
      PERd % 226.8 226.8 228.0 228.0 229.2 229.2
    Tbiv (bivalente temperatuur) COPd   3.40 3.40 3.25 3.25 3.44 3.44
      Pdh kW 11.1 11.1 12.4 12.4 12.2 12.2
      PERd % 136.0 136.0 130.0 130.0 137.6 137.6
      Tbiv °C 2 2 2 2 4 4
    D-conditie (12°C DB/11°C NB) Cdh (degradatie-verwarming)   0.94 0.94 0.94 0.94 0.94 0.94
      COPd   7.60 7.60 7.78 7.78 8.03 8.03
      Pdh kW 5.2 5.2 5.3 5.3 5.3 5.3
      PERd % 304.0 304.0 311.2 311.2 321.2 321.2
Opmerkingen (1) - Toestand 1: koelen Ta 35°C - LWE 18°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Toestand 1: koelen Ta 35°C - LWE 18°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Toestand 1: koelen Ta 35°C - LWE 18°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Toestand 1: koelen Ta 35°C - LWE 18°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Toestand 1: koelen Ta 35°C - LWE 18°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Toestand 1: koelen Ta 35°C - LWE 18°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 35°C (DT = 5°C)
  (2) - Toestand 2: koelen Ta 35°C - LWE 7°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Toestand 2: koelen Ta 35°C - LWE 7°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Toestand 2: koelen Ta 35°C - LWE 7°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Toestand 2: koelen Ta 35°C - LWE 7°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Toestand 2: koelen Ta 35°C - LWE 7°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 45°C (DT = 5°C) (2) - Toestand 2: koelen Ta 35°C - LWE 7°C (DT = 5°C); verwarmen Ta DB/NB 7°C/6°C - LWC 45°C (DT = 5°C)