FCQG71FVEB / RZQSG71L2V1B FCQG100FVEB / RZQSG100L7Y1B FCQG100FVEB / RZQSG100L7V1B FCQG100FVEB / RZQSG100L7Y1B9 FCQG125FVEB / RZQSG125L7Y1B FCQG125FVEB / RZQSG125L7V1B FCQG125FVEB / RZQSG125L7Y1B9
Poff (uitgeschakeld) W 0.0   0.0 0.0   0.0 0.0
Koelen Psb (koeling in stand-by) W 7.0   7.0 7.0   7.0 7.0
  Cooling-=-Cooling cdc degradation cooling 0.25   0.25 0.25   0.25 0.25
Seizoensrendement (volgens EN14825) Koelen Pdesign kW 6.80   9.50 9.50   12.00 12.00
    Jaarlijks energieverbruik kWu 466   650.685 650.685   821.918 821.918
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class 5.11 5.11 (6) 5.11 5.11 5.11 (6) 5.11 5.11
    D voorwaarden (20℃ - 27/19) Pdc kW 3.63   3.99 3.99   3.98 3.98
      Opgenomen vermogen kW 0.42   0.49 0.48   0.40 0.40
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 8.62   8.10 8.27   10.05 10.04
    C voorwaarden (25℃ - 27/19) Opgenomen vermogen kW 0.56   0.78 0.77   0.84 0.84
      Pdc kW 3.51   4.56 4.56   5.69 5.69
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 6.28   5.81 5.90   6.81 6.77
    A voorwaarden (35°C - 27/19) Opgenomen vermogen kW 2.19   2.88 2.88   4.12 4.12
      Pdc kW 6.80   9.50 9.50   12.00 12.00
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 3.10   3.30 3.30   2.91 2.91
    B voorwaarden (30℃ - 27/19) Pdc kW 5.01   7.00 7.00   8.84 8.84
      Opgenomen vermogen kW 1.27   1.53 1.59   2.86 2.83
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 3.94   4.58 4.40   3.10 3.12
  Verwarming (gematigd klimaat) Jaarlijks energieverbruik kWu 2,327   2,799 2,799   2,949 2,949
    Pdesign kW 6.33   7.60 7.60   8.03 8.03
    Min. vermogen backupverwarming bij ontwerpvoorwdn kW 0.58   0.53 0.53   0.73 0.69
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scop a A 3.80 (6) A A 3.81 (6) A A
    TBivalent Pdh (verwarmingsvermogen) kW 5.60   6.72 6.72   7.10 7.10
      Opgenomen vermogen kW     2.09 2.10   2.41 2.43
      Tbiv (bivalente temperatuur) °C -7   -7 -7   -7 -7
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 2.25   3.21 3.20   2.94 2.93
    C voorwaarden (7℃) Pdh (verwarmingsvermogen) kW 2.89   3.06 3.05   3.07 3.07
      Opgenomen vermogen kW     0.56 0.56   0.55 0.56
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 5.85   5.45 5.50   5.54 5.52
    TOL TOL (bedrijfstemperatuur) °C -15   -15 -15   -15 -15
      Pdh (beschikbaar verwarmingsvermogen) kW 6.00   7.66 7.66   7.64 7.74
      Opgenomen vermogen kW 3.24   3.70 3.83   3.65 3.69
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 1.85   2.07 2.03   2.09 2.10
    A voorwaarden (-7°C) Pdh (verwarmingsvermogen) kW 5.60   6.72 6.72   7.10 7.10
      Opgenomen vermogen kW     2.09 2.10   2.41 2.43
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 2.25   3.21 3.20   2.94 2.93
    D voorwaarden (12℃) Pdh (verwarmingsvermogen) kW 3.28   3.49 3.49   3.50 3.50
      Opgenomen vermogen kW     0.54 0.54   0.54 0.54
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 6.73   6.43 6.48   6.53 6.50
    B voorwaarden (2°C) Opgenomen vermogen kW     1.48 1.48   1.46 1.45
      Pdh (verwarmingsvermogen) kW 4.06   5.07 5.07   5.07 5.07
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 3.82   3.43 3.41   3.47 3.49
Koelcapaciteit Nom. kW 6.8 9.5 (3) 9.5 9.5 12.0 (3) 12.0 12.0
Pck (verwarming krukkast) W 0.0   0.0 0.0   0.0 0.0
Nominaal energierendement Jaarlijks energieverbruik kWu 971 (0.000) 1,440 (0.000) 1,440 (0.000) 1,440 (0.000) 1,870 (0.000) 1,870 (0.000) 1,870 (0.000)
  Richtlijn Energielabels Verwarming A A A A A A A
  Nominal efficiency-=-Cop 3.21 3.30 3.30 3.30 3.21 3.21 3.21
Verwarmen Psb (verwarming in stand-by) W     14.0 14.0   14.0 14.0
  Heating-=-Heating cdh degradation heating 0.25   0.25 0.25   0.25 0.25
Verwarmingscapaciteit Nom. kW 7.5 10.8 (4) 10.8 10.8 13.5 (4) 13.5 13.5
Pto (Thermostat off) W 34.0   109.0 109.0   97.0 97.0
Opgenomen vermogen Koelen Nom. kW   2.88     3.74    
  Verwarmen Nom. kW   3.05     3.96    
Koud seizoen inbegrepen Ja   Ja Ja   Ja Ja
Opmerkingen EER/COP volgens Eurovent 2012, alleen voor gebruik buiten de EU Jaarlijks energieverbruik: op basis van een gemiddelde van 500 bedrijfsuren per jaar bij vollast (nominale omstandigheden) EER/COP volgens Eurovent 2012, alleen voor gebruik buiten de EU EER/COP volgens Eurovent 2012, alleen voor gebruik buiten de EU Jaarlijks energieverbruik: op basis van een gemiddelde van 500 bedrijfsuren per jaar bij vollast (nominale omstandigheden) EER/COP volgens Eurovent 2012, alleen voor gebruik buiten de EU EER/COP volgens Eurovent 2012, alleen voor gebruik buiten de EU
  Nominaal rendement: koeling tegen 35°/27° nominale belasting, verwarming tegen 7°/20° nominale belasting Energielabel: schaalverdeling van A (meest efficiënt) tot G (minst efficiënt) Nominaal rendement: koeling tegen 35°/27° nominale belasting, verwarming tegen 7°/20° nominale belasting Nominaal rendement: koeling tegen 35°/27° nominale belasting, verwarming tegen 7°/20° nominale belasting Energielabel: schaalverdeling van A (meest efficiënt) tot G (minst efficiënt) Nominaal rendement: koeling tegen 35°/27° nominale belasting, verwarming tegen 7°/20° nominale belasting Nominaal rendement: koeling tegen 35°/27° nominale belasting, verwarming tegen 7°/20° nominale belasting
    Koelen: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB; equivalente leidinglengte: 5 m; hoogteverschil: 0m     Koelen: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB; equivalente leidinglengte: 5 m; hoogteverschil: 0m    
    Verwarmen: binnentemp. 20°CDB; buitentemp. 7°CDB/6°CWB; equivalente koelmiddelleidinglengte: 5 m; hoogteverschil: 0m     Verwarmen: binnentemp. 20°CDB; buitentemp. 7°CDB/6°CWB; equivalente koelmiddelleidinglengte: 5 m; hoogteverschil: 0m    
    Jaarlijks energieverbruik is conform richtlijn 2002/31/EC inzake energielabels     Jaarlijks energieverbruik is conform richtlijn 2002/31/EC inzake energielabels    
    SEER en SCOP zijn conform EN 14825     SEER en SCOP zijn conform EN 14825    
    Nominaal rendement: koeling tegen 35°/27° nominale belasting, verwarming tegen 7°/20° nominale belasting     Nominaal rendement: koeling tegen 35°/27° nominale belasting, verwarming tegen 7°/20° nominale belasting