| RXYSA8AMY1B | RXYSA10AMY1B | RXYSA12AMY1B | RXYSA4A7Y1B (Archived) | RXYSA5A7Y1B (Archived) | RXYSA6A7Y1B (Archived) | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| Aanbevolen combinatie | 4 x FXSA50A2VEB | 4 x FXSA63A2VEB | 6 x FXSA50A2VEB | 3 x FXSA25A2VEB + 1 x FXSA32A2VEB | 4 x FXSA32A2VEB | 2 x FXSA32A2VEB + 2 x FXSA40A2VEB | ||||
| Aanbevolen combinatie 2 | 4 x FXFA50A2VEB | 4 x FXFA63A2VEB | 6 x FXFA50A2VEB | |||||||
| Aanbevolen combinatie 3 | 4 x FXMA50A5VEB | 4 x FXMA63A5VEB | 6 x FXMA50A5VEB | |||||||
| Koelvermogen | Prated, c | kW | 22.4 (1) | 28 | 33.5 (1) | 12.1 (1) | 14.0 (1) | 15.5 (1) | ||
| Verwarmingsvermogen | Prated,h | kW | 22.4 (2) | 28 | 33.5 (2) | 12.1 (2) | 14.0 (2) | 15.5 (2) | ||
| Nom. | 6°CNB | kW | 22.4 (2) | 28 | 33.5 (2) | 12.1 (2) | 14.0 (2) | 15.5 (2) | ||
| COP bij nom. vermogen | 6°C NB | KW/KW | 3.47 (2) | 3.83 (2) | 3.82 (2) | 4.49 | 4.20 | 4.10 | ||
| SEER | 6.36 | 6.93 | 6.47 | 7.9 | 7.4 | 7.3 | ||||
| SEER aanbevolen combinatie 2 | 7.14 | 7.13 | 7.07 | |||||||
| SEER aanbevolen combinatie 3 | 6.86 | 7.04 | 6.88 | |||||||
| SCOP | 4.42 | 4.42 | 4.64 | 4.9 | 4.5 | 4.5 | ||||
| SCOP aanbevolen combinatie 2 | 4.44 | 4.42 | 4.66 | |||||||
| SCOP aanbevolen combinatie 3 | 4.46 | 4.46 | 4.7 | |||||||
| Koeling | A-voorwaarden (35 °C – 27/19) | EERd | 2.38 | 2.94 | 2.47 | 3.4 | 3.1 | 3.0 | ||
| Pdc | kW | 22.4 | 28 | 33.5 | 12.1 | 14.0 | 15.5 | |||
| B-voorwaarden (30 °C – 27/19) | EERd | 4.09 | 4.9 | 4.39 | 5.6 | 5.1 | 4.8 | |||
| Pdc | kW | 16.5 | 20.6 | 24.7 | 8.9 | 10.3 | 11.4 | |||
| C-voorwaarden (25 °C – 27/19) | EERd | 7.56 | 7.21 | 6.86 | 10.4 | 9.5 | 9.3 | |||
| Pdc | kW | 10.6 | 13.3 | 15.9 | 5.7 | 6.6 | 7.3 | |||
| D-voorwaarden (20 °C – 27/19) | EERd | 17.33 | 18.5 | 19.2 | 17.5 | 17.5 | 17.9 | |||
| Pdc | kW | 4.7 | 5.9 | 7.1 | 4.9 | 4.5 | 4.9 | |||
| Koeling aanbevolen combinatie 2 | A-voorwaarde (35 °C – 27/19) | EERd | 2.86 | 3 | 2.88 | |||||
| Pdc | kW | 22.4 | 28 | 33.5 | ||||||
| B-voorwaarde (30 °C – 27/19) | EERd | 4.74 | 4.99 | 4.69 | ||||||
| Pdc | kW | 16.5 | 20.6 | 24.7 | ||||||
| C-voorwaarde (25 °C – 27/19) | EERd | 8.42 | 7.73 | 7.71 | ||||||
| Pdc | kW | 10.6 | 13.3 | 15.9 | ||||||
| D-voorwaarde (20 °C – 27/19) | EERd | 18.05 | 18.82 | 20.08 | ||||||
| Pdc | kW | 5.3 | 7.3 | 7.8 | ||||||
| Koeling aanbevolen combinatie 3 | A-voorwaarde (35 °C – 27/19) | EERd | 2.62 | 3.04 | 2.68 | |||||
| Pdc | kW | 22.4 | 28 | 33.5 | ||||||
| B-voorwaarde (30 °C – 27/19) | EERd | 4.63 | 4.77 | 4.54 | ||||||
| Pdc | kW | 16.5 | 20.6 | 24.7 | ||||||
| C-voorwaarde (25 °C – 27/19) | EERd | 8.07 | 7.21 | 7.51 | ||||||
| Pdc | kW | 10.6 | 13.3 | 15.9 | ||||||
| D-voorwaarde (20 °C – 27/19) | EERd | 16.98 | 21.9 | 19.98 | ||||||
| Pdc | kW | 5.1 | 7.1 | 7.1 | ||||||
| Verwarming (gematigd klimaat) | Tbivalent | COPd (beschikbaar prestatiecoëfficiënt) | 2.21 | 2.23 | 2.2 | 2.7 | 2.5 | 2.4 | ||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 14.9 | 19.6 | 23.5 | 8.4 | 9.7 | 10.7 | |||
| Tbiv (bivalente temperatuur) | °C | -10 | -10 | -10 | -10 | -10 | -10 | |||
| Verwarming van ruimtes (gematigd klimaat) | Omstandigheid E (-10°C) | COPd (beschikbaar prestatiecoëfficiënt) | 2.21 | 2.23 | 2.2 | 2.7 | 2.5 | 2.4 | ||
| TOL | Pdh (beschikbaar verwarmingsvermogen) | kW | 14.9 | 19.6 | 23.5 | 8.4 | 9.7 | 10.7 | ||
| Verwarming (gematigd klimaat) | TOL | TOL (bedrijfstemperatuur) | °C | -10 | -10 | -10 | -10 | -10 | -10 | |
| A-voorwaarden (-7 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 2.52 | 2.62 | 2.71 | 3.3 | 2.8 | 2.8 | |||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 13.2 | 17.4 | 20.8 | 7.4 | 8.5 | 9.5 | |||
| B-voorwaarden (2 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 4.32 | 4.47 | 4.63 | 4.7 | 4.3 | 4.1 | |||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 8 | 10.6 | 12.7 | 4.5 | 5.2 | 5.8 | |||
| C-voorwaarden (7 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 6.32 | 6.16 | 6.51 | 6.8 | 6.5 | 6.5 | |||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 5.2 | 6.8 | 8.1 | 3.3 | 3.3 | 3.7 | |||
| D-voorwaarden (12 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 6.95 | 5.56 | 6.34 | 8.6 | 8.4 | 8.7 | |||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 2.9 | 4.7 | 4.8 | 3.9 | 3.9 | 4.0 | |||
| Verwarming (gematigd klimaat) aanbevolen combinatie 2 | TBivalent | COPd (beschikbaar prestatiecoëfficiënt) | 2.31 | 2.3 | 2.18 | |||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 14.9 | 19.6 | 23.5 | ||||||
| Tbiv (bivalente temperatuur) | °C | -10 | -10 | -10 | ||||||
| TOL | COPd (beschikbaar prestatiecoëfficiënt) | 2.31 | 2.3 | 2.18 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 14.9 | 19.6 | 23.5 | ||||||
| TOL (bedrijfstemperatuur) | °C | -10 | -10 | -10 | ||||||
| A-voorwaarde (-7 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 2.6 | 2.7 | 2.77 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 13.2 | 17.4 | 20.8 | ||||||
| B voorwaarden (2°C) | COPd (beschikbaar prestatiecoëfficiënt) | 4.42 | 4.45 | 4.66 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 8 | 10.6 | 12.7 | ||||||
| C-voorwaarde (7 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 6.08 | 6.05 | 6.46 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 5.2 | 6.8 | 8.1 | ||||||
| D-voorwaarde (12 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 6.6 | 5.52 | 6.11 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 2.9 | 4.5 | 4.5 | ||||||
| Verwarming (gematigd klimaat) aanbevolen combinatie 3 | TBivalent | COPd (beschikbaar prestatiecoëfficiënt) | 2.25 | 2.27 | 2.18 | |||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 14.9 | 19.6 | 23.5 | ||||||
| Tbiv (bivalente temperatuur) | °C | -10 | -10 | -10 | ||||||
| TOL | COPd (beschikbaar prestatiecoëfficiënt) | 2.25 | 2.27 | 2.18 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 14.9 | 19.6 | 23.5 | ||||||
| TOL (bedrijfstemperatuur) | °C | -10 | -10 | -10 | ||||||
| A-voorwaarde (-7 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 2.56 | 2.7 | 2.77 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 13.2 | 17.4 | 20.8 | ||||||
| B voorwaarden (2°C) | COPd (beschikbaar prestatiecoëfficiënt) | 4.4 | 4.47 | 4.69 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 8 | 10.6 | 12.7 | ||||||
| C-voorwaarde (7 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 6.26 | 6.19 | 6.54 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 5.2 | 6.8 | 8.1 | ||||||
| D-voorwaarde (12 °C) | COPd (beschikbaar prestatiecoëfficiënt) | 7.11 | 5.72 | 6.48 | ||||||
| Pdh (beschikbaar verwarmingsvermogen) | kW | 3.2 | 4.7 | 4.9 | ||||||
| Capaciteitsbereik | PK | 8 | 10 | 12 | 4 | 5 | 6 | |||
| Maximaal aantal aansluitbare binnenunits | 26 (3) | 32 (3) | 39 (3) | 13 (3) | 16 (3) | 18 (3) | ||||
| Index-aansluiting binnen | Min. | 100 | 125 | 150 | 50.0 | 62.5 | 70.0 | |||
| Nom. | 100 | 125 | 140 | |||||||
| Max. | 260 | 325 | 390 | 130.0 | 162.5 | 182.0 | ||||
| Afmetingen | Unit | Hoogte | mm | 1430 | 1615 | 1615 | 869 | 869 | 869 | |
| Breedte | mm | 940 | 940 | 940 | 1100 | 1100 | 1100 | |||
| Diepte | mm | 320 | 460 | 460 | 460 | 460 | 460 | |||
| Gewicht | Unit | kg | 134 | 163 | 163 | 102 | 102 | 102 | ||
| Ventilator | Externe statische druk | Max. | Pa | 35 | 35 | 35 | 45 | 45 | 45 | |
| Compressor | Type | Hermetisch gesloten scrollcompressor | Hermetisch gesloten scrollcompressor | Hermetisch gesloten scrollcompressor | Hermetisch gesloten swingcompressor | Hermetisch gesloten swingcompressor | Hermetisch gesloten swingcompressor | |||
| Bedrijfsbereik | Koelen | Min. | °C DB | -5 | -5 | -5 | -5 | -5 | -5 | |
| Max. | °C DB | 52 | 52 | 52 | 46 | 46 | 46 | |||
| Werkingsbereik | Verwarmen | Min. | °CWB | -20 | -20 | -20 | -20 | -20 | -20 | |
| Max. | °CWB | 15.5 | 15.5 | 15.5 | 16 | 16 | 16 | |||
| Geluidsvermogenniveau | Koelen | Nom. | dBA | 73.2 (4) | 74 | 76.1 (4) | 67.0 (4) | 68.1 (4) | 69.0 (4) | |
| Geluidsdrukniveau | Koelen | Nom. | dBA | 58.1 (5) | 57 | 60 | 49.0 (6) | 51.0 (6) | 51.0 (6) | |
| Koelmiddel | Type | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | |||
| GWP | 675 | 675 | 675 | 675.0 | 675.0 | 675.0 | ||||
| Koudemiddel | Vulling | tCO2Eq | 3.51 | 4.73 | 4.79 | 2.30 | 2.30 | 2.30 | ||
| Koelmiddel | Vulling | kg | 5.2 | 7 | 7.1 | 3.40 | 3.40 | 3.40 | ||
| Leidingaansluitingen | Vloeistof | Type | Hardsoldeerverbinding | Hardsoldeerverbinding | Hardsoldeerverbinding | Hardsoldeerverbinding | Hardsoldeerverbinding | Hardsoldeerverbinding | ||
| Buitendiameter | mm | 9.52 | 9.52 | 12.7 | 10 | 10 | 10 | |||
| Gas | Type | Hardsoldeerverbinding | Hardsoldeerverbinding | Hardsoldeerverbinding | Hardsoldeerverbinding | Hardsoldeerverbinding | Hardsoldeerverbinding | |||
| Buitendiameter | mm | 19.1 | 19.1 | 22.2 | 15.9 | 15.9 | 15.9 | |||
| Totale leidinglengte | Systeem | Werkelijk | m | 300 (6) | 300 (6) | 300 (6) | 300 (7) | 300 (7) | 300 (7) | |
| Niveauverschil: | OU - IU | Buitenunit op de hoogste positie | m | 50 | 50 | 50 | ||||
| Binnenunit op de hoogste positie | m | 40 | 40 | 40 | ||||||
| Standaard-accessoires | Aansluitleidingen | 1 | 2 | 1 | ||||||
| Montage- en bedieningshandleiding | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Voeding | Naam | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 | |||
| Fase | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | ||||
| Spanningsvoeding | Frequentie | Hz | 50/60 | 50/60 | 50/60 | 50 | 50 | 50 | ||
| Spanning | V | 380-415/400 | 380-415/400 | 380-415/400 | 380-415 | 380-415 | 380-415 | |||
| Opmerkingen | (1) - Koelen: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB; equivalente leidinglengte: 7,5m; hoogteverschil: 0m | (1) - Koelen: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB; equivalente leidinglengte: 7,5m; hoogteverschil: 0m | (1) - Koelen: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB; equivalente leidinglengte: 7,5m; hoogteverschil: 0m | (1) - Koelen: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB; equivalente leidinglengte: 7,5m; hoogteverschil: 0m | (1) - Koelen: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB; equivalente leidinglengte: 7,5m; hoogteverschil: 0m | (1) - Koelen: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB; equivalente leidinglengte: 7,5m; hoogteverschil: 0m | ||||
| (2) - Verwarmen: binnentemp. 20°CDB; buitentemp. 7°CDB/6°CWB; equivalente koelmiddelleidinglengte: 7,5m; hoogteverschil: 0m | (2) - Verwarmen: binnentemp. 20°CDB; buitentemp. 7°CDB/6°CWB; equivalente koelmiddelleidinglengte: 7,5m; hoogteverschil: 0m | (2) - Verwarmen: binnentemp. 20°CDB; buitentemp. 7°CDB/6°CWB; equivalente koelmiddelleidinglengte: 7,5m; hoogteverschil: 0m | (2) - Verwarmen: binnentemp. 20°CDB; buitentemp. 7°CDB/6°CWB; equivalente koelmiddelleidinglengte: 7,5m; hoogteverschil: 0m | (2) - Verwarmen: binnentemp. 20°CDB; buitentemp. 7°CDB/6°CWB; equivalente koelmiddelleidinglengte: 7,5m; hoogteverschil: 0m | (2) - Verwarmen: binnentemp. 20°CDB; buitentemp. 7°CDB/6°CWB; equivalente koelmiddelleidinglengte: 7,5m; hoogteverschil: 0m | |||||
| (3) - Het reële aantal units hangt af van de aansluitverhouding en de beperkingen voor het systeem. | (3) - Het reële aantal units hangt af van de aansluitverhouding en de beperkingen voor het systeem. | (3) - Het reële aantal units hangt af van de aansluitverhouding en de beperkingen voor het systeem. | (3) - Het reële aantal units hangt af van de aansluitverhouding en de beperkingen voor het systeem. | (3) - Het reële aantal units hangt af van de aansluitverhouding en de beperkingen voor het systeem. | (3) - Het reële aantal units hangt af van de aansluitverhouding en de beperkingen voor het systeem. | |||||
| (4) - Het geluidsvermogenniveau is een absolute waarde die door een geluidsbron wordt opgewekt. | (4) - Het geluidsvermogenniveau is een absolute waarde die door een geluidsbron wordt opgewekt. | (4) - Het geluidsvermogenniveau is een absolute waarde die door een geluidsbron wordt opgewekt. | (4) - Het geluidsvermogenniveau is een absolute waarde die door een geluidsbron wordt opgewekt. | (4) - Het geluidsvermogenniveau is een absolute waarde die door een geluidsbron wordt opgewekt. | (4) - Het geluidsvermogenniveau is een absolute waarde die door een geluidsbron wordt opgewekt. | |||||
| (5) - Het geluidsdrukniveau is een relatieve waarde, die afhankelijk is van de afstand en de akoestische omgeving. Zie de geluidsniveautekeningen voor meer bijzonderheden. | (5) - Het geluidsdrukniveau is een relatieve waarde, die afhankelijk is van de afstand en de akoestische omgeving. Zie de geluidsniveautekeningen voor meer bijzonderheden. | (5) - Het geluidsdrukniveau is een relatieve waarde, die afhankelijk is van de afstand en de akoestische omgeving. Zie de geluidsniveautekeningen voor meer bijzonderheden. | (5) - Volgens ENER Lot 21 | (5) - Volgens ENER Lot 21 | (5) - Volgens ENER Lot 21 | |||||
| (6) - Zie 'Selectie van koelmiddelleiding' of montagehandleiding | (6) - Zie 'Selectie van koelmiddelleiding' of montagehandleiding | (6) - Zie 'Selectie van koelmiddelleiding' of montagehandleiding | (6) - Het geluidsdrukniveau is een relatieve waarde, die afhankelijk is van de afstand en de akoestische omgeving. Zie de geluidsniveautekeningen voor meer bijzonderheden. | (6) - Het geluidsdrukniveau is een relatieve waarde, die afhankelijk is van de afstand en de akoestische omgeving. Zie de geluidsniveautekeningen voor meer bijzonderheden. | (6) - Het geluidsdrukniveau is een relatieve waarde, die afhankelijk is van de afstand en de akoestische omgeving. Zie de geluidsniveautekeningen voor meer bijzonderheden. | |||||
| (7) - RLA is gebaseerd op de volgende condities: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB | (7) - RLA is gebaseerd op de volgende condities: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB | (7) - RLA is gebaseerd op de volgende condities: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB | (7) - Zie 'Selectie van koelmiddelleiding' of montagehandleiding | (7) - Zie 'Selectie van koelmiddelleiding' of montagehandleiding | (7) - Zie 'Selectie van koelmiddelleiding' of montagehandleiding | |||||
| (8) - In overeenstemming met EN/IEC 61000-3-12 kan het nodig zijn contact op te nemen met de distributienetbeheerder, om te verzekeren dat de apparatuur is aangesloten op een voeding waarvan de Ssc gelijk is aan of groter is dan de minimale Ssc-waarde. | (8) - In overeenstemming met EN/IEC 61000-3-12 kan het nodig zijn contact op te nemen met de distributienetbeheerder, om te verzekeren dat de apparatuur is aangesloten op een voeding waarvan de Ssc gelijk is aan of groter is dan de minimale Ssc-waarde. | (8) - In overeenstemming met EN/IEC 61000-3-12 kan het nodig zijn contact op te nemen met de distributienetbeheerder, om te verzekeren dat de apparatuur is aangesloten op een voeding waarvan de Ssc gelijk is aan of groter is dan de minimale Ssc-waarde. | (8) - RLA is gebaseerd op de volgende condities: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB | (8) - RLA is gebaseerd op de volgende condities: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB | (8) - RLA is gebaseerd op de volgende condities: binnentemp. 27°CDB, 19°CWB; buitentemperatuur. 35°CDB | |||||
| (9) - MCA moet worden gebruikt om draden van de juiste diameter te kiezen. De MCA kan worden beschouwd als de maximale bedrijfsstroom. | (9) - MCA moet worden gebruikt om draden van de juiste diameter te kiezen. De MCA kan worden beschouwd als de maximale bedrijfsstroom. | (9) - MCA moet worden gebruikt om draden van de juiste diameter te kiezen. De MCA kan worden beschouwd als de maximale bedrijfsstroom. | (9) - MSC is de maximaalstroom tijdens de aanloop van de compressor. VRV IV gebruikt alleen invertercompressors. De opstartstroom is altijd ≤ max. bedrijfsstroom. | (9) - MSC is de maximaalstroom tijdens de aanloop van de compressor. VRV IV gebruikt alleen invertercompressors. De opstartstroom is altijd ≤ max. bedrijfsstroom. | (9) - MSC is de maximaalstroom tijdens de aanloop van de compressor. VRV IV gebruikt alleen invertercompressors. De opstartstroom is altijd ≤ max. bedrijfsstroom. | |||||
| (10) - MFA wordt gebruikt voor de selectie van de stroomonderbreker en de aardingsschakelaar (aardlekschakelaar). | (10) - MFA wordt gebruikt voor de selectie van de stroomonderbreker en de aardingsschakelaar (aardlekschakelaar). | (10) - MFA wordt gebruikt voor de selectie van de stroomonderbreker en de aardingsschakelaar (aardlekschakelaar). | (10) - MCA moet worden gebruikt om draden van de juiste diameter te kiezen. De MCA kan worden beschouwd als de maximale bedrijfsstroom. | (10) - MCA moet worden gebruikt om draden van de juiste diameter te kiezen. De MCA kan worden beschouwd als de maximale bedrijfsstroom. | (10) - MCA moet worden gebruikt om draden van de juiste diameter te kiezen. De MCA kan worden beschouwd als de maximale bedrijfsstroom. | |||||
| Standaard-accessoires | Waarschuwingslabel | 1 | 1 | 1 | ||||||
| Koelmiddellabel voor wetgeving inzake F-gas | 1 | 1 | 1 | |||||||
| Hulpleidingenset | 1 | 1 | 1 | |||||||
| General safety precautions | 1 | 1 | 1 | |||||||
| Peel off F-gas label | 1 | 1 | 1 | |||||||
| Kabelbinders | 2 | 2 | 2 | |||||||
| Opmerkingen | (11) - MFA wordt gebruikt voor de selectie van de stroomonderbreker en de aardingsschakelaar (aardlekschakelaar). | (11) - MFA wordt gebruikt voor de selectie van de stroomonderbreker en de aardingsschakelaar (aardlekschakelaar). | (11) - MFA wordt gebruikt voor de selectie van de stroomonderbreker en de aardingsschakelaar (aardlekschakelaar). | |||||||
| (12) - TOCA geeft de totale waarde weer van elke overbelastingsinstelling. | (12) - TOCA geeft de totale waarde weer van elke overbelastingsinstelling. | (12) - TOCA geeft de totale waarde weer van elke overbelastingsinstelling. | ||||||||
| (13) - FLA betekent de nominale bedrijfsstroom van de ventilator. | (13) - FLA betekent de nominale bedrijfsstroom van de ventilator. | (13) - FLA betekent de nominale bedrijfsstroom van de ventilator. | ||||||||